Multi-Functional Clamp Leakage Current Meter for Accurate AC/DC Measurement
Multi-Functional Clamp Leakage Current Meter for Accurate AC/DC Measurement - ETCR6640 Free standard shipping to supported destinations. See the shipping policy for preparation and transit estimates.
Need help choosing? Tell us what you need to measure.
Shipping & returns
Shipping & returns
Free standard shipping is available to supported destinations. Delivery time includes order preparation and transit and varies by destination. See our shipping policy for current delivery estimates and availability.
See our return policy for return conditions. For an order-specific delivery question, contact Mcooh.
Multi-Functional Clamp Leakage Current Meter for Accurate AC/DC Measurement - ETCR6640 Free standard shipping to supported destinations. See the shipping policy for preparation and transit estimates.
Choosing the right instrument?
Tell us your measurement range, material or target, and operating conditions.
Description
Description
The ETCR6640, ETCR6670, and ETCR6680 leakage current clamp meters suit electrical testing jobs that involve checking AC leakage current, assessing earth leakage, or examining current harmonics. Choose an option by matching its listed AC current range and clamp opening to the conductors you need to measure.
Compare the AC measuring ranges and resolution in the table when selecting a model. It does not establish the DC measurement limits. Check the manual for DC specifications before choosing this instrument for a DC leakage testing job.
Choose the Configuration for Your Measurement
- AC current range: Match the option to your measurement needs: ETCR6640 lists AC 0.00mA–300A, ETCR6670 lists AC 0.00mA–1200A, and ETCR6680 lists AC 0.00mA–2000A.
- Clamp opening: Check conductor fit before ordering. Listed CT sizes are Φ40mm for ETCR6640, Φ70mm for ETCR6670, and 80mmX80mm for ETCR6680.
- Low-current readings: The table lists AC 0.01mA resolution for each option. Check the specifications or manual for accuracy at the leakage current level you need to measure; resolution alone does not establish accuracy.
- Filter setting: The listed frequency bands are 40Hz–70Hz with the filter open and 40Hz–1kHz with the filter close. Check which setting suits your measurement before use.
- Power and display: The meter uses a rechargeable lithium battery and includes an LCD backlight, spotlight, and data hold. A charge adaptor is included.
Order Options
| Select an option | SKU |
|---|---|
| ETCR6640 | INS05-ET1025 |
| ETCR6670 | INS05-ET1026 |
| ETCR6680 | INS05-ET1027 |
Product Details and Specifications
Description
-
Versatile Measurement Capabilities
The Clamp Leakage Current Meter is designed for precise measurement of AC and DC leakage currents. Whether you need to assess earth leakage or perform harmonic tests, this meter meets all your requirements efficiently. -
High-Performance Clamp Technology
Featuring a clamp jaw made of permalloy and advanced magnetic shielding technology, this leakage current meter ensures minimal interference from external electromagnetic fields. Use the stated range, frequency and accuracy conditions for the selected model when interpreting a result. -
Comprehensive Testing Features
Equipped with true RMS measurement capability, the meter offers a band pass filter function along with maximum, minimum, and average value displays. Additional features include harmonic testing, aberration rate assessment, and more, making it an essential tool for electrical testing professionals. -
User-Friendly Design
This clamp meter comes with a rechargeable high-capacity lithium battery, ensuring long-lasting use. With a backlight for visibility in low-light environments, a spotlight function for focused lighting, data hold capabilities, and Bluetooth communication for data transfer, it enhances user convenience and functionality.
Technical Specifications
|
Model |
ETCR6640 |
ETCR6670 |
ETCR6680 |
|
Range |
AC 0.00mA~300A |
AC 0.00mA~1200A |
AC 0.00mA~2000A |
|
Resolution |
AC 0.01mA |
AC 0.01mA |
AC 0.01mA |
|
Max Accuracy |
±1.5%rdg±5dgt |
±1.5%rdg±5dgt |
±1.5%rdg±5dgt |
|
CT Size |
Φ40mm |
Φ70mm |
80mmX80mm |
|
Meter Dimension |
192mmX96mmX40mm |
237mmX131mmX40mm |
253mmX145mmX40mm |
|
Weight |
256g (include battery) |
477g (include battery) |
664g (include battery) |
|
Power Supply |
Rechargeable lithium battery DC3.7V/1000mAh |
||
|
LCD Size |
43mmX38mm; display area: 36.5mmX29mm |
||
|
LCD Backlight |
Yes |
||
|
Spotlight |
Yes |
||
|
Filter Function |
Filter open: 40Hz~70Hz; Filter close: 40Hz~1kHz |
||
|
Harmonic Analysis |
21times (above 10mA) |
||
|
Distortion Rate |
Yes (above 10mA) |
||
|
Max/Min Value |
Yes |
||
|
Average Value |
Yes |
||
|
Data Hold |
Yes |
||
|
Data Storage |
2000 groups (Store via APP) |
||
|
Overflow Display |
Exceed measure range overflow function: “OL ” symbol display |
||
|
Bluetooth Communication |
Yes, can test or view the test results on mobile after install the APP. |
||
|
Automatic Shutdown |
5 minutes after power on, will shutdown automatically without any operation to reduce the power consumption. |
||
|
Working Current |
60mA (open spotlight 72mA) |
||
|
Line Voltage |
Below 600V line test |
||
|
Working Condition |
-10℃~50℃; below 80%RH |
||
|
Dielectric Strength |
AC 3700V/rms(between the core and shell) |
||
|
Accessories |
Meter: 1PCS; Charge adaptor: 1PCS; Tool bag: 1PCS |
||
Questions Before Ordering
Does the specification table confirm a DC leakage current range?
No. The ranges and resolution in this page's specifications cover AC measurements. Check the manual for DC range and accuracy before ordering for DC measurements.
Can this leakage current meter perform harmonic testing?
The specifications list harmonic analysis and distortion rate measurement above 10mA. Check the manual if harmonic testing is needed at or below that current level.
Can I view and save readings on a phone?
Bluetooth communication lets you test or view results on a mobile device after installing the APP. The specifications list storage of 2000 groups via the APP.